Shopping security
The Honeywell FC-SAI-1620m is a compact, high-density Safe Analog Input Module designed for the Honeywell Safety Manager platform. This module supports 16 analog channels, providing precise acquisition of process signals for safety-critical applications. The “m” designation indicates monitored operation, offering enhanced diagnostics and continuous verification of field sensor integrity.
High Precision and Safety
SIL 3 Certified: Suitable for Safety Integrity Level 3 analog loops, ensuring maximum reliability for emergency shutdown and critical interlocks.
12-Bit Resolution: Accurate Analog-to-Digital conversion for 4–20 mA transmitters, supporting pressure, temperature, and flow measurement.
Redundant Operation: Can be paired for high-availability configurations, maintaining operation if one module fails.
Advanced Monitoring Capabilities
Monitored Channels: Continuously checks 4–20 mA loop integrity for open circuits, short circuits, or over-range/under-range conditions.
HART Pass-Through: Compatible with HART-enabled devices, enabling remote diagnostics and calibration without interrupting the process.
Robust Electrical Design
Galvanic Isolation: Protects the Safety Manager bus from field-side electrical interference and ground loops.
Low Thermal Output: Efficient design reduces heat in dense control cabinets, extending module lifespan.
Internal Self-Tests: Periodically verifies A/D conversion and reference voltages to maintain measurement accuracy within safety limits.
Maintenance-Friendly Design
Hot-Swappable: Can be replaced online in redundant configurations, avoiding downtime.
LED Diagnostics: Front-panel LEDs display module health and channel status for quick troubleshooting.
| Feature | Specification |
|---|---|
| Model Number | FC-SAI-1620m |
| Input Type | 4–20 mA Analog |
| Number of Channels | 16 |
| Resolution | 12-bit |
| Accuracy | ±0.1% of full scale (25°C) |
| Input Impedance | 250 Ω typical |
| Operating Voltage | 24 VDC |
| Operating Temperature | -5°C to +70°C (+23°F to +158°F) |
| Dimensions (H x W x D) | 2 x 19 x 12.8 cm (0.8″ x 7.5″ x 5″) |
| Weight | 0.14 kg |
| Safety Level | SIL 3 |
| Country of Origin | USA |
| Warranty | 12 months |
Emergency Shutdown (ESD): Monitoring critical pressure, temperature, or flow trip signals.
Fire & Gas Systems (F&G): Analog gas detection and flame monitoring for hazardous areas.
Critical Process Interlocks: Ensures analog values remain within safe limits before allowing process continuation.
Q: Can the FC-SAI-1620m support HART-enabled devices?
A: Yes, it provides pass-through HART communication for calibration and diagnostics.
Q: Is hot-swapping supported?
A: Yes, in redundant systems the module can be replaced online without process disruption.
Q: What is the maximum number of channels per module?
A: The module supports 16 analog channels, each monitored for integrity.
Comparison with Similar Models
FC-SAI-1616: Basic analog input module without monitored features.
FC-SAI-1620: Standard 16-channel analog input, “non-monitored” version for less critical loops.
Ships within 48 hours · Estimated delivery Jul 1 - Jul 6
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order