The Honeywell FC-USI-0001 is a Universal Serial Interface (USI) module engineered for use with Safety Manager and FSC (Fail Safe Control) systems. It acts as a secure communication bridge between safety controllers and external devices, enabling safe and reliable data exchange without compromising the integrity of the safety system.
Designed for non-safety communication tasks, the module facilitates reporting of alarms, diagnostic status, and process variables to supervisory systems such as DCS, PLCs, or HMIs. Its built-in electrical isolation ensures that faults in external devices cannot affect safety-critical controller operations.
Multi-Protocol Support
Configurable for RS232, RS422, or RS485 (2-wire or 4-wire) interfaces.
Supports standard industrial protocols, including Modbus RTU (Master/Slave), for seamless integration with third-party systems.
High Reliability and Isolation
Provides robust galvanic isolation between the Safety Manager backplane and external communication lines.
Designed for high-reliability SIL-rated environments, ensuring dependable operation within safety systems.
Flexible Configuration
Adjustable baud rates from 300 to 19,200 (and higher depending on configuration).
Parameters such as parity, stop bits, and station addresses are configured via Honeywell Safety Builder software.
Efficient Data Handling
Internal buffers optimize data transmission and reception without overloading the main Safety Manager processor.
Front-panel LEDs (TX/RX) offer immediate visual feedback of communication activity and module health.
| Feature | Specification |
|---|---|
| Model Number | FC-USI-0001 |
| Module Type | Universal Serial Interface (USI) |
| Interface Options | RS232, RS422, RS485 (2-wire/4-wire) |
| Channels | 2 Independent Channels |
| Maximum Cable Length | 15 m (RS232), 1200 m (RS422/485) |
| Power Supply | 5 V DC, 450 mA (internal) |
| Operating Temperature | 0°C to +60°C (32°F to +140°F) |
| System Compatibility | Honeywell Safety Manager / FSC |
| Memory | 8 MB Flash, 4 MB Local SRAM, 256 KB Shared RAM |
| Processor | Motorola 8260 Communication Processor |
| Communication Ports | 2 Dual-Speed Fast Ethernet, 2 Serial Channels |
| Weight | 0.8 kg |
| Dimensions | 12.7 cm × 12.7 cm × 12.7 cm |
| Origin | USA |
Linking Honeywell Safety Manager systems to HMIs or DCS for monitoring and reporting.
Safe transmission of non-critical safety data such as alarms, diagnostics, and process values.
Integration into standalone or Experion PKS/PlantScape systems.
Q: Can this module connect to multiple external devices simultaneously?
A: Yes, it supports two independent serial channels configurable for RS232, RS422, or RS485.
Q: Does it support Modbus protocol?
A: Yes, it supports Modbus RTU as both Master and Slave.
Q: How is configuration handled?
A: All communication parameters, including baud rate, parity, stop bits, and addresses, are set via Honeywell Safety Builder software.
Q: Is this module suitable for SIL-rated systems?
A: Yes, it is designed for use within Honeywell SIL-rated Safety Manager and FSC environments.